產品資訊 > 單相工業級低頻隔離不斷電系統 > 工業級雙轉換單相低頻雙隔離在線式 ON-LINE UPS TU-8KVA~100KVA

工業級雙轉換單相低頻雙隔離在線式 ON-LINE UPS TU-8KVA~100KVA

工業級雙轉換單相低頻雙隔離在線式 ON-LINE UPS TU-8KVA~100KVA

Model
TU-系列
Capacity
8KVA
10KVA
12KVA
15KVA
20KVA
25KVA
30KVA
40KVA
50KVA
60KVA
80KVA
100KVA
Input
Voltage
110V.220V.208/120V.190/110V.380/220V.440V.480VAC
Frequency
50Hz or 60Hz ± 5%
Phase
1P2W+G / 3P3W+G / 3P4W+G
Power Factor
0.8~1
Output
Voltage
110VAC or 220VAC ± 1%
Phase
1P2W+G or 1P3W+G
Voltage Regulation
± 1% at linear load
Frequency
50Hz or 60Hz ± 0.5%
Waveform Distortion
Pure Sine Wave less than 3% at full load
Crest Factor
3:1
Overload Capacity
100% ~ 124% continuous, >125% for 25 seconds, >150% to bypass
Efficiency AC to AC
>80% at battery fully charge
Battery
Type
Rechargeable, sealed maintenance free
Backup Time
10 minutes at full load and 25 minutes at half load
Recharge Time
4 ~ 8 hours 90% after fully discharge
Transfer Time
MainInverter
No break
Indicator
LCD Display
Input/Output & Battery Voltage, Frequency, Output Load, Operation Temperature
LED Display
Mimic display
Audible Alarm
Mains Fail
Sounds every 4 seconds after line fails
Battery Low
Sounds every second when approaches battery low level
UPS Fault
Continuous alarm
Protection
Short Circuit
When a short circuit occurs, the UPS will not transfer to Bypass but emit a sustained tone. Once the short circuit is removed, the tone stops and the whole system operates normally again. The UPS stops supplying power if the period of a short circuit is longer 3 seconds.
Lightning : Yes    Surge : Yes
Environment
Temperature
0C ~ 40C
Humidity
0% ~ 90%, non-condensing
Communication
Interface Port
RS-232 or DB9
W*D*H
UPS
460*690*1150mm
650*800*1690mm
Net Weight
UPS
220kgs
250kgs
270kgs
300kgs
330kgs
340kgs
360kgs
370kgs
390kgs
400kgs
420kgs
480kgs