產品資訊 > 單相工業級低頻隔離不斷電系統 > 工業級雙轉換單相低頻雙隔離在線式 ON-LINE UPS TU-3KVA~6.25KVA

工業級雙轉換單相低頻雙隔離在線式 ON-LINE UPS TU-3KVA~6.25KVA
Model
|
TU-系列
|
|||||||||||||
Capacity
|
3.75KVA
|
5KVA
|
6KVA
|
6.25KVA
|
||||||||||
Input
|
Voltage
|
110V.220VAC
|
||||||||||||
Frequency
|
50Hz or 60Hz ± 5%
|
|||||||||||||
Phase
|
1P2W+G
|
|||||||||||||
Power Factor
|
0.8~1
|
|||||||||||||
Output
|
Voltage
|
110VAC or 220VAC ± 1%
|
||||||||||||
Phase
|
1P2W+G or 1P3W+G
|
|||||||||||||
Voltage Regulation
|
± 1% at linear load
|
|||||||||||||
Frequency
|
50Hz or 60Hz ± 0.5%
|
|||||||||||||
Waveform Distortion
|
Pure Sine Wave less than 3% at full load
|
|||||||||||||
Crest Factor
|
3:1
|
|||||||||||||
Overload Capacity
|
100% ~ 124% continuous, >125% for 25 seconds, >150% to bypass
|
|||||||||||||
Efficiency AC to AC
|
>80% at battery fully charge
|
|||||||||||||
Battery
|
Type
|
Rechargeable, sealed maintenance free
|
||||||||||||
Backup Time
|
10 minutes at full load and 25 minutes at half load
|
|||||||||||||
Recharge Time
|
4 ~ 8 hours 90% after fully discharge
|
|||||||||||||
Transfer Time
|
MainInverter
|
No break
|
||||||||||||
LED Display
|
Mimic display
|
|||||||||||||
Audible Alarm
|
Mains Fail
|
Sounds every 4 seconds after line fails
|
||||||||||||
Battery Low
|
Sounds every second when approaches battery low level
|
|||||||||||||
UPS Fault
|
Continuous alarm
|
|||||||||||||
Protection
|
Short Circuit
|
When a short circuit occurs, the UPS will not transfer to Bypass but emit a sustained tone. Once the short circuit is removed, the tone stops and the whole system operates normally again. The UPS stops supplying power if the period of a short circuit is longer 3 seconds.
|
||||||||||||
Lightning : Yes Surge : Yes
|
||||||||||||||
Environment
|
Temperature
|
0゚C ~ 40゚C
|
||||||||||||
Humidity
|
0% ~ 90%, non-condensing
|
|||||||||||||
Communication
|
Interface Port
|
DB9
|
||||||||||||
W*D*H
|
UPS
|
265*630*760mm
|
||||||||||||
Net Weight
|
UPS
|
110kgs
|
120kgs
|
130kgs
|
140kgs
|
150kgs
|